Three readings tell you most of what is wrong with a piston (fixed orifice) air conditioner: evaporator TD, superheat and subcooling. Here is how to read them – plus a free two-page field card to print.
The example numbers below are for one set of conditions: return-air wet bulb 66°F and outdoor 85°F, which gives a target superheat of 15°F. All temperatures are in °F. Always work from the conditions on site.
1. Three key readings
Evaporator TD
Return air − supply air
Shows cooling performance. Normal ≈ 20°F. Too small → not cooling; too large → low airflow.
Superheat (SH)
Suction line temp − evaporator saturation temp
Is the evaporator starved? (low side). Find the target first from wet bulb + outdoor temp. ▲ High → short of refrigerant; ▼ Low → floodback risk.
Subcooling (SC)
Condensing saturation temp − liquid line temp
Is liquid backing up? (high side). Example normal ≈ 8°F. ▼ Low → undercharged; ▲ High → restriction or overcharge.
2. Quick diagnosis table
| Condition | TD | Superheat | Subcooling | Other signs |
|---|---|---|---|---|
| ✓ Normal | ≈ 20°F | ≈ target (15°F) | ≈ 8°F | — |
| Low airflow | ▲ High (28°F) | ▼ Very low (2°F) | Little change | Very cold coil and suction line; floodback risk |
| Undercharged | ▼ Low (10°F) | ▲ High (25°F) | ▼ Low (2°F) | Low suction pressure; warm suction line |
| Restriction | ▼ Low | ▲ High (25°F) | ▲ High (17°F) | Suction pressure may look normal; compressor can overheat and trip |
3. Easy to mix up: undercharge vs. restriction
Both show high superheat – subcooling tells them apart.
Superheat ▲ High + subcooling ▼ Low
→ Undercharged: fix the leak, then charge
Superheat ▲ High + subcooling ▲ High
→ Restriction: do not add refrigerant
4. Field reminders
- Read temperatures, not just pressures. A pressure only means something once it is converted to saturation temperature. With a restriction the gauges can look normal; superheat gives it away.
- On piston systems, charge by superheat and recalculate the target every time. The hotter it is outside and the more humid inside, the higher the target.
- Watch subcooling while charging. If a small amount of refrigerant doubles subcooling but the low side does not move, stop: the refrigerant is just stacking up in the condenser.
5. Where and how to measure
| Reading | What to measure | Formula | Example |
|---|---|---|---|
| TD | ① Return air, ② supply air at the register closest to the indoor unit (probe thermometer) | ① − ② | 75 − 55 = 20°F |
| Superheat | ③ Low-side pressure, converted to evaporator saturation temp (PT chart or digital manifold); ④ suction line temp. Target from ① wet bulb + ⑦ outdoor temp (slide chart or app) | ④ − ③ sat. temp | 60 − 45 = 15°F |
| Subcooling | ⑤ High-side pressure, converted to condensing saturation temp; ⑥ liquid line temp | ⑤ sat. temp − ⑥ | 100 − 92 = 8°F |
Measuring tips
- Let the system run 10–15 minutes and record once the readings are steady.
- Set the gauges or digital manifold to the right refrigerant (for example R-410A), or the saturation temperatures will be wrong.
- Put pipe clamps on clean copper near the outdoor unit's service valves, clamp them tight, insulate them and keep them out of direct sun.
- Take wet bulb at the return grille, and outdoor temperature in the shade on the condenser's air inlet side.